Looking at the Wikipedia page on thermocouples I found this table:
TypeTemperature range °C (continuous)Temperature range °C (short term)Tolerance class one (°C)Tolerance class two (°C)IEC Color codeBS Color codeANSI Color code
K0 to +1100−180 to +1300±1.5 between −40 °C and 375 °C
±0.004×T between 375 °C and 1000 °C
±2.5 between −40 °C and 333 °C
±0.0075×T between 333 °C and 1200 °C
IEC Type K Thermocouple.svg
BS Type K Thermocouple.svg
MC 96.1 K Thermocouple Grade Color Code.svg
J0 to +750−180 to +800±1.5 between −40 °C and 375 °C
±0.004×T between 375 °C and 750 °C
±2.5 between −40 °C and 333 °C
±0.0075×T between 333 °C and 750 °C
IEC Type J Thermocouple.svg
BS Type J Thermocouple.svg
MC 96.1 J Thermocouple Grade Color Code.svg
N0 to +1100−270 to +1300±1.5 between −40 °C and 375 °C
±0.004×T between 375 °C and 1000 °C
±2.5 between −40 °C and 333 °C
±0.0075×T between 333 °C and 1200 °C
IEC Type N Thermocouple.svg
BS Type N Thermocouple.svg
MC 96.1 N Thermocouple Grade Color Code.svg
R0 to +1600−50 to +1700±1.0 between 0 °C and 1100 °C
±[1 + 0.003×(T − 1100)] between 1100 °C and 1600 °C
±1.5 between 0 °C and 600 °C
±0.0025×T between 600 °C and 1600 °C
BS Type N Thermocouple.svg
BS Type R Thermocouple.svg
Not defined.
S0 to 1600−50 to +1750±1.0 between 0 °C and 1100 °C
±[1 + 0.003×(T − 1100)] between 1100 °C and 1600 °C
±1.5 between 0 °C and 600 °C
±0.0025×T between 600 °C and 1600 °C
BS Type R Thermocouple.svg
Not defined.
B+200 to +17000 to +1820Not Available±0.0025×T between 600 °C and 1700 °CNo standard use copper wireNo standard use copper wireNot defined.
T−185 to +300−250 to +400±0.5 between −40 °C and 125 °C
±0.004×T between 125 °C and 350 °C
±1.0 between −40 °C and 133 °C
±0.0075×T between 133 °C and 350 °C
IEC Type T Thermocouple.svg
BS Type T Thermocouple.svg
MC 96.1 T Thermocouple Grade Color Code.svg
E0 to +800−40 to +900±1.5 between −40 °C and 375 °C
±0.004×T between 375 °C and 800 °C
±2.5 between −40 °C and 333 °C
±0.0075×T between 333 °C and 900 °C
IEC Type E Thermocouple.svg
BS Type E Thermocouple.svg
MC 96.1 E Thermocouple Grade Color Code.svg
Chromel/AuFe−272 to +300n/aReproducibility 0.2% of the voltage; each sensor needs individual calibration.